Siemens 0.7 W, 110V, 240 V, 6A Communication Module

Subtotal (1 unit)*

HK$3,876.10

Add to Basket
Select or type quantity
In Stock
  • 3 unit(s) ready to ship from another location
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +HK$3,876.10

*price indicative

RS Stock No.:
213-0015
Mfr. Part No.:
3UF7300-1AU00-0
Manufacturer:
Siemens
Find similar products by selecting one or more attributes.
Select all

Brand

Siemens

Product Type

Communication Module

Supply Voltage

110V, 240V

Output Voltage

120V

Current Rating

6A

Power Rating

0.7W

Overall Length

92mm

Overall Width

22.5mm

Overall Depth

124mm

IP Rating

IP20

Minimum Operating Temperature

-25°C

Maximum Operating Temperature

60°C

Standards/Approvals

EAC

COO (Country of Origin):
DE

Siemens 3UF Series Communication Module, 110 to 240V Supply Voltage, 0.7W Power - 3UF7300-1AU00-0


This communication module is a digital Interface for automation systems that provides four configurable digital inputs and two monostable relay outputs. Designed for use with a compatible Basic unit, it accepts 110 to 240 V AC/DC supply and delivers a 120 V output for control signalling. The unit is Compact and intended for DIN-rail mounting in control panels where Compact, low-power modules are required.

Features and Benefits:


• 6 A continuous relay current enabling moderate load switching
• 0.7 W consumption reducing panel power draw
• IP20 protection suitable for enclosed electrical cabinets
• −25 °C to 60 °C operating range for varied industrial climates
• 200 m maximum digital signal wiring for extended reach

Applications


• Suitable for motor protection and starter control systems
• Ideal for integration into automation systems with Basic units
• Used with control panels requiring DIN-rail mounting
• Can be used for signalling and contactor switching tasks
• Suitable for installations requiring EAC-approved modules

How many inputs and outputs does the unit provide?


It offers four parameterisable digital inputs and two relay outputs.

What connection types are provided for control wiring?


Removable screw-type terminals accept solid and stranded conductors with specified cross-sections.

What short-circuit protection options are recommended per output?


Use gG 6 A fuses, quick-response 10 A fuses, or specified miniature circuit-breaker settings.

What mechanical and electrical endurance figures apply to the relays?


Typical mechanical life is 10,000,000 cycles and electrical endurance is 100,000 cycles.

What electromagnetic immunity and emission performance does it meet?


It complies with IEC emission and immunity levels including burst, surge and HF radiation ratings.